Where the survey stands

4 boundaries: 1 verified, 2 with open defects, 1 needing reassessment

  • Defects open2
  • Reassessment needed1
  • Verified1

16 items on the register: 7 satisfactory, 1 repaired and accepted, 6 open defects (1 urgent), 1 could not be assessed, 1 not surveyed yet

2 things need reassessment after an alteration.

On the planBoundaries and items, floor by floor
Plant roomStoreKitchenCorridorStair 1LiftlobbyLiftWCsReceptionStair 2EXITEXITEXITPlan of the ground floor
CW-G-01 · 60 min · VerifiedCW-G-02 · 60 min · Defects open
  • Defects open
  • Reassessment needed
  • Not fully inspected
  • Not surveyed
  • Verified
  • Satisfactory
  • Defect
  • Urgent defect
  • Could not assess
  • Not surveyed

Tap a boundary or an item to find it in the lists below. Every state is also written on the plan and in the lists.

Boundaries44 boundaries: 1 verified, 2 with open defects, 1 needing reassessment
  • CF-1-01 · Compartment floor

    First floor slab, between ground and first floor. Between ground floor and first floor

    Reassessment needed
    Required fire resistance
    60 min
    Design reference
    Fire strategy FS-02 rev C (fictional), drawing FS-101
    Floor
    First floor

    Outstanding (2)

    • CF-1-01: altered since it was surveyed, needs another look
    • SP-1-02: altered since it was surveyed, needs another look

    Sections

    • Open-plan officeInspected
    • Meeting roomInspected
    • Riser cupboardInspected
    • CorridorInspected

    Items (4)

    Add an item to CF-1-01

    Doors (0)

    • CW-1-01 · Compartment wall

      First, server room enclosure. Between server room and corridor, archive store and tea point

      Defects open
      Required fire resistance
      60 min
      Design reference
      Fire strategy FS-02 rev C (fictional), drawing FS-101
      Floor
      First floor

      Remedial works: 5, 1 accepted.Handover pack for CW-1-01

      Outstanding (11)

      • CB-1-01: open defect
      • SP-1-01: open defect
      • SP-1-04: open defect
      • SP-1-05: open defect
      • FD-1-03: open defect on the door
      • SP-1-04: rework required on the remedial work
      • SP-1-01: pre-cover check not recorded yet (hold point)
      • SP-1-01: open snags or actions on the remedial work
      • SP-1-04: open snags or actions on the remedial work
      • CB-1-01: work completed, awaiting verification
      • Tea point side: partly inspected. Ceiling void above the tea point seen from one tile only.

      Sections

      • Server room sideInspected
      • Corridor sideInspected
      • Archive store sideInspected
      • Tea point sidePartly inspected

      Doors (1)

    • CW-G-01 · Compartment wall

      Ground, Stair 1 enclosure. Between stair 1 and corridor and lift lobby

      Verified
      Required fire resistance
      60 min
      Design reference
      Fire strategy FS-02 rev C (fictional), drawing FS-101
      Floor
      Ground floor

      Verified: nothing outstanding

      Every section is inspected, every linked item is satisfactory, every linked door is signed and in date, and nothing has been altered since.

      Sections

      • Stair sideInspected
      • Corridor sideInspected
      • Lift lobby sideInspected

      Items (2)

      Add an item to CW-G-01

      Doors (1)

    • CW-G-02 · Compartment wall

      Ground, service riser enclosure. Between service riser and corridor, lift lobby and wcs

      Defects open
      Required fire resistance
      60 min
      Design reference
      Fire strategy FS-02 rev C (fictional), drawing FS-101
      Floor
      Ground floor

      Outstanding (4)

      • SP-G-02: open defect
      • SP-G-03: open defect
      • Inside the riser: inaccessible. Riser cupboard locked, no key on site. Key holder back Monday.
      • FD-G-07: door inspection overdue

      Sections

      • Corridor sideInspected
      • Lift lobby sideInspected
      • Inside the riserInaccessible
      • WC sideInspected

      Items (2)

      Add an item to CW-G-02

      Doors (1)

    Register16Every item, with filters

    16 items shown of 16.

    • SP-1-01Service penetrationUrgent defectContractor: In progressFirst, corridor, server room wall at high level
      Open the record for SP-1-01

      First floor · in CW-1-01

      Construction: Cable tray through 140 mm blockwork, about 200 by 100 mm opening

      Finding: Large unsealed opening round the cable tray, about 200 by 100 mm

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

      Remedial work with Northgate Doorsets · open

    • SP-1-03Service penetrationRepaired, work acceptedFirst, corridor, server room wall at high level
      Open the record for SP-1-03

      First floor · in CW-1-01

      Construction: Two 15 mm copper refrigerant pipes for the server room cooling

      Finding: Gap round both pipes filled with expanding foam only

      Signed by Priya Nair (Level 3 passive fire protection inspection), 22 Oct 2026

      Remedial work with Northgate Doorsets · accepted 24 Oct 2026

    • SP-G-02Service penetrationDefect, high priorityGround, corridor, riser wall at low level
      Open the record for SP-G-02

      Ground floor · in CW-G-02

      Construction: Two 110 mm plastic waste pipes through 140 mm blockwork

      Finding: No collars on two 110 mm plastic pipes; open gap round both

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

      Book remedial work on SP-G-02
    • CB-1-01Cavity barrierDefect, medium priorityContractor: CompletedVerification: Awaiting verificationFirst, tea point, ceiling void on the server room line
      Open the record for CB-1-01

      First floor · in CW-1-01

      Construction: Calcium silicate board cavity barrier

      Finding: Barrier board loose, gap of about 30 mm at the outside wall end

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

      Remedial work with Northgate Doorsets · open

    • SP-1-04Service penetrationDefect, medium priorityContractor: In progressVerification: Rework requiredFirst, archive store, server room wall at low level
      Open the record for SP-1-04

      First floor · in CW-1-01

      Construction: About 20 data cables in a 100 mm sleeve

      Finding: Sleeve not sealed at either end

      Signed by Priya Nair (Level 3 passive fire protection inspection), 22 Oct 2026

      Remedial work with Northgate Doorsets · open

    • SP-1-05Service penetrationDefect, low priorityContractor: BookedFirst, tea point, server room wall at low level
      Open the record for SP-1-05

      First floor · in CW-1-01

      Construction: Single 20 mm data cable

      Finding: Open gap of about 5 mm round the cable

      Signed by Priya Nair (Level 3 passive fire protection inspection), 22 Oct 2026

      Remedial work with Northgate Doorsets · open

    • SP-G-03Service penetrationDefect, low priorityGround, WCs, riser wall above the ceiling
      Open the record for SP-G-03

      Ground floor · in CW-G-02

      Construction: 100 mm steel ventilation duct, fire damper

      Finding: Damper access panel missing its fixing screws

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

      Book remedial work on SP-G-03
    • CB-G-01Cavity barrierCould not assessGround, reception, ceiling void on the WC line
      Open the record for CB-G-01

      Ground floor · not linked to a boundary

      Construction: Cavity barrier as drawn on the fire strategy (not seen)

      Finding: Ceiling tiles are fixed; the barrier could not be seen

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • LJ-1-01Linear jointSatisfactoryFirst, corridor, head of the server room wall
      Open the record for LJ-1-01

      First floor · in CW-1-01

      Construction: Head-of-wall joint, 15 mm, fire-rated sealant

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • LJ-1-02Linear jointSatisfactoryFirst, meeting room, slab edge at the outside wall
      Open the record for LJ-1-02

      First floor · in CF-1-01

      Construction: Slab edge seal, mineral wool and sealant

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • LJ-G-01Linear jointSatisfactoryGround, corridor, head of the Stair 1 wall
      Open the record for LJ-G-01

      Ground floor · in CW-G-01

      Construction: Head-of-wall joint, 20 mm, fire-rated sealant over mineral wool

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • SF-1-01Structural fire protectionSatisfactoryFirst, open-plan office, steel beam under the roof
      Open the record for SF-1-01

      First floor · in CF-1-01

      Construction: Steel beam, board encasement, 60 minute system

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • SF-G-01Structural fire protectionSatisfactoryGround, reception, steel column supporting the first floor
      Open the record for SF-G-01

      Ground floor · in CF-1-01

      Construction: Steel column, intumescent paint, 60 minute system

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • SP-1-02Service penetrationSatisfactoryNeeds reassessmentFirst, riser cupboard, floor
      Open the record for SP-1-02

      First floor · in CF-1-01

      Construction: Service bundle through the slab, batt and mastic seal

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

      Altered on 26 Oct 2026: New hole cored through the riser floor for a fibre cable, next to SP-1-02. Needs another look.

    • SP-G-01Service penetrationSatisfactoryGround, lift lobby, Stair 1 wall at high level
      Open the record for SP-G-01

      Ground floor · in CW-G-01

      Construction: Two data cables in a 25 mm sleeve, intumescent sealant

      Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026

    • SP-G-04Service penetrationNot surveyedGround, kitchen, corridor wall (from the fire-stopping schedule)
      Open the record for SP-G-04

      Ground floor · not linked to a boundary

      Construction: Gas pipe sleeve, as scheduled

      On the register from Sam Whitfield, 20 Oct 2026. Not surveyed yet.

    Rooms and what was inspected236 limitations

    Ground floor

    • Plant roomNot surveyedOutside this survey: the landlord surveys the plant room separately.Priya Nair, 21 Oct 2026
    • StoreNothing recorded
    • KitchenNothing recorded
    • CorridorInspectedPriya Nair, 21 Oct 2026
    • Stair 1InspectedPriya Nair, 21 Oct 2026
    • Lift lobbyInspectedPriya Nair, 21 Oct 2026
    • LiftNothing recorded
    • Service riserInaccessibleRiser cupboard locked, no key on site. Key holder back Monday.Priya Nair, 21 Oct 2026
    • WCsInspectedPriya Nair, 21 Oct 2026
    • ReceptionPartly inspectedCeiling void seen at two tiles only; the rest are fixed.Priya Nair, 21 Oct 2026
    • Stair 2Nothing recorded

    First floor

    • Archive storeInspectedPriya Nair, 21 Oct 2026
    • Server roomInspectedPriya Nair, 21 Oct 2026
    • Tea pointPartly inspectedCeiling void above the tea point seen from one tile only.Priya Nair, 21 Oct 2026
    • CorridorInspectedPriya Nair, 21 Oct 2026
    • Stair 1Nothing recorded
    • Lift lobbyNothing recorded
    • LiftNothing recorded
    • Riser cupboardInspectedPriya Nair, 21 Oct 2026
    • WCsNothing recorded
    • Open-plan officeInspectedPriya Nair, 21 Oct 2026
    • Meeting roomInspectedPriya Nair, 21 Oct 2026
    • Stair 2Nothing recorded
    Alterations1Flagged for reassessment
    • New hole cored through the riser floor for a fibre cable, next to SP-1-02

      First floor · Dan Ellis, 26 Oct 2026 · flags CF-1-01, SP-1-02 for reassessment

    More information