Planning and reports
Service penetration · Ground, corridor, riser wall at low level
Intrusive work can start (Intrusive fire-stopping). HH-AR-01 was reviewed for adjustment, ironmongery, seals, glazing, intrusive fire-stopping, cutting or drilling into compartment walls by Sam Whitfield (BOHS P405 Management of asbestos in buildings). Follow the restrictions below.
Hand tools only on frames. Do not drill, sand or cut the plant room door surround (FD-G-05): textured coating sample S3 contains asbestos. Stop and tell the manager if you find any material you are unsure of. For fire-stopping, cut out old sealant by hand: no power tools on wall linings.
From HH-AR-01, reviewed by Sam Whitfield
Dated 18 Aug 2025, by Thorne Environmental (fictional)
Not covered: Roof void; lift shaft
Not accessed: Service riser behind FD-G-07 (locked on the day)
1 photo from every inspection, fault, repair and upload, newest first. Tap one to see it full screen.
Full inspection
Signed, competent inspector
A survey finding signed by a competent surveyor.
Signed by a competent surveyor: Priya Nair.
Report a fault
Report, not a defect
Anyone on the building: what is wrong, a photo if you can, how urgent. The manager decides what happens. It is not a defect until then.
Report a faultDefect, high priority
No collars on two 110 mm plastic pipes; open gap round both
Signed by Priya Nair (Level 3 passive fire protection inspection), 21 Oct 2026
No remedial work booked.