Barrier board loose, gap of about 30 mm at the outside wall end
Completed is the contractor's word. Only a named verifier, never the contractor's firm, can accept the work.
In boundary CW-1-01, 60 minutes required
Intrusive work can start (Intrusive fire-stopping, works wk-seed-03). HH-RS-02 was reviewed for intrusive fire-stopping, cutting or drilling into compartment walls by Sam Whitfield (BOHS P405 Management of asbestos in buildings). Follow the restrictions below.
No asbestos found in the server room wall or its linings (samples S6 to S9). Do not open the ceiling over the open-plan office: it was not surveyed.
From HH-RS-02, reviewed by Sam Whitfield
Dated 20 Oct 2026, by Calloway Surveys Ltd (fictional)
Not covered: Server room floor void; above the suspended ceiling in the open-plan office
Not accessed: Riser cupboard (locked on the day)
Dated 15 Oct 2026, by Calloway Surveys Ltd (fictional)
Not covered: Above the suspended ceiling in the open-plan office
Will this work cut, drill or disturb the building fabric (walls, floors, ceilings, linings, frames or existing materials)?
Yes, as booked by Sam Whitfield on 22 Oct 2026
Booked as: Yes
Signed as Sam Whitfield, BOHS P405 Management of asbestos in buildings.
Kept on the record and in the audit pack.
Pre-cover check recorded· Above a ceiling
Ready to cover, checked by Priya Nair (Level 3 passive fire protection inspection), 25 Oct 2026. Board fixed at 300 mm centres, wall end sealed, no gaps seen
No differences from the specified detail in what was recorded.
| Measurement | Specified | As installed |
|---|---|---|
| Gap at the edges | 5 mm | 3 mm |
| Board or barrier thickness | 12 mm | 12 mm |
| Fixing centres | 300 mm | 300 mm |
Recorded by Dan Ellis, 24 Oct 2026
For example EI 60
What the wall or floor is actually built of
Dan Ellis, 24 Oct 2026: Loose board, 30 mm gap at the outside wall
Dan Ellis, 24 Oct 2026: Board re-fixed, sealant at the wall end
Dan Ellis, 26 Oct 2026: Ceiling tiles back
Opening the camera…
Photos are saved on this device.
No works certificate on the record. The handover lists this as a limitation.
The installer's certificate is kept as evidence. It does not accept the work: only the named verifier does.
No snags or actions.
Completed by Dan Ellis, 26 Oct 2026
Waiting for Priya Nair, the verifier named at booking. Only they can verify it; you can change the verifier under Booking.